Orderline: +44 (0) 1278 452277
Items:
Value:

Quick Search
 


 

Metal Frame Laminar Flow HEPA


  Jasun Filtration |  Absolute Filters H10 to U15 |  Panels and Laminar Flow HEPA Filters |  Metal Frame Laminar Flow HEPA


45mm Thick Filter Grade H11

45mm Thick Filter Grade H11 45mm Thick Minipleat Lamiar Flow HEPA filters with Extruded Aluminium Frame, Grades H10/H11

Aluminium Frame HEPA Filters 68mm Thick

Aluminium Frame HEPA Filters 68mm Thick 68mm Thick Minipleat Lamiar Flow HEPA filters with Extruded Aluminium Frame, Grades H10/H11, H13 and H14

Aluminium Frame HEPA Filters 78mm Thick

Aluminium Frame HEPA Filters 78mm Thick 78mm Thick Minipleat Lamiar Flow HEPA filters with Extruded Aluminium Frame, Grades H10/H11, H13 and H14

Aluminium Frame HEPA Filters 88mm Thick

Aluminium Frame HEPA Filters 88mm Thick 88mm Thick Minipleat Lamiar Flow HEPA filters with Extruded Aluminium Frame, Grades H10/H11, H13 and H14

ULTIMA GEL To view or print the PDF please Click Here

Liquid Seal Absolute Laminar Flow Filters

TYPICAL APPLICATIONS
To be used for absolute air filtration in controlled contamination environments,
clean rooms, laminar flow benches and operating theatres using gel seal.


TECHNICAL SPECIFICATION
MEDIA = Glass fibre paper.
SEPARATORS = Cotton threads with hot melt gluing.
FRAME = Anodized aluminium profile 80 mm deep.
FACE GUARDS = Epoxy painted expanded aluminium grids on both sides.
SEALANT = Two components cold moulded polyurethane.
SEAL = Polyurethane gel.
GASKET = One piece cold moulded expanded polyurethane.

EFFICIENCY H10 to U15

TESTING = Each filter individually tested.
TEMPERATURE = 80°C max.
RELATIVE HUMIDITY = 100% max.
OPTIONS = Antibacterial treatment on request.





Ultima GEL Seal HEPA Filter


ULTIMA KE To view or print the PDF please Click Here
Knife Edge Absolute Laminar Flow Filters

TYPICAL APPLICATIONS
To be used for absolute air filtration in clean-rooms. Laminar flow benches,
equipped for the “liquid seal” method.


TECHNICAL SPECIFICATION
MEDIA = Glass fibre paper.
SEPARATORS = Cotton threads with hot melt gluing.
FRAME = Anodized aluminium profile with knife edge 35 mm deep.
FACE GUARDS = Epoxy painted expanded aluminium grids on both sides.
SEALANT = Two components cold moulded polyurethane.


EFFICIENCY: H10 to U15

TESTING = Each filter individually tested.
TEMPERATURE = 80°C max.
RELATIVE HUMIDITY = 100% max.
OPTIONS = Antibacterial treatment on request.





Ultima KE (Knife Edge) HEPA Filter